The burning area is the item most likely to be "simply cancelled" in any dispute. Cancel it and joss paper turns up in every corner of the columbarium: beside the planters, under the stairs, in the corner of the car park. Cancelling does not solve the problem; making it a separate, negative-pressure room does.

The burning room must be a separate room with a fire resistance of no less than 2 hours Use 200 mm aerated concrete block, or double-layer gypsum board with 50 mm rock wool between.
The most important sentence: it must not share a wall with the niche area. A shared wall means any leak of heat or flue gas goes straight into the storage space If you build it, build it at the end of the columbarium, on an external wall.
Area is set by the number of burners: a single burner plus operating space, no less than 12 m²; two burners, no less than 20 m².
This is the core of the whole thing. Supply 1,000 m³/h and extract 1,150. Once the pressure differential is established, air at the door gaps flows inward and smoke does not escape.
Design for 20 air changes per hour. The flue must rise at least 3 m above the roof and be at least 10 m from the fresh-air intake — on columbarium drawings these two ducts constantly collide, so fix the flue outlet first and the intake second.
Insulate the ducting and provide an access hatch every 6 m. Ash build-up is a fire risk: leave it a year and the duct wall carries 2–3 mm.
Estimate total niches divided by 500, then add one spare. A 2,000-niche columbarium gets three (two duty, one spare); 5,000 niches gets about ten.
The count is also affected by local practice: some regions burn only in a concentrated burst at Qingming, so the columbarium must size for the hourly rate on the peak day rather than the annual average.
Furnace temperature above 800 °C with a two-second residence time in the secondary chamber are the basic conditions for reducing black smoke. A cheap single-chamber burner produces black smoke that the families themselves find unbearable.
Use 60-litre lidded ash bins in a fire-resistant material Ash raked from the furnace can be above 200 °C and must stand alone for 24 hours before handling.
The ash-clearing hatch and the family deposit hatch must be separate, on opposite sides of the room. Families only move on one side of the burning area; ash is removed from the other, and the two routes never cross This is the easiest thing to get wrong — get it wrong and the cleaning staff push an ash cart through the crowd every day.

Provide two 4 kg dry powder extinguishers, one at the door and one beside the burner. Fit heat detectors connected to the fire alarm panel.
I do not recommend sprinklers. The reason is practical: activation lifts the ash into a wet slurry that sticks to walls and ductwork, is extremely expensive to clean, and is corrosive.
Keep combustibles out of the room. Store joss paper in a separate room behind a fire wall, with stock not exceeding three days' usage — once joss paper piles up in a columbarium it is the single largest ignition source.
Families come in from the aisle, deposit, bow with palms together, and leave never turning back. The deposit hatch is 900–1,000 high, 400 wide, with a closable fire-rated flap.
No threshold at the door, but a 20 mm water return upstand so that hosing the floor does not send water out into the columbarium aisle.
Some jurisdictions have banned open or semi-open burning There are two routes.
First, centralised burning on behalf of families. The columbarium burns at two fixed times daily; families hand the joss paper to the service desk and it is logged by number. Publishing the times and the process is far more effective than the word "prohibited."
Second, electronic substitution Install a blessing wall or an electronic burner with QR-code messages and a display. It is not a full substitute, but it diverts part of the demand, especially among younger visitors.
Q: Can the burning room have a window?
A: A high-level window (sill above 2 m) for emergency smoke relief is acceptable, normally closed, with a self-closing device.
Q: Will the flue condense and drip?
A: Yes. Insulate the duct, provide a drain at the lowest point, and inspect quarterly.
Q: How many doors does the burning room need?
A: Two. One on the family deposit side, one on the ash side, never open at the same time.

A joss paper burning area is essentially a negative-pressure room: a separate 2-hour fire wall, extract 15% above supply, 20 air changes, one burner per 500 niches, ash cooled 24 hours, two doors splitting the flows. In columbarium culture, burning is not pollution — it is a ritual step that has to be taken seriously. Giving it a proper room solves the problem far better than a "no burning" sign on the door.