Escape width is the last thing that should be judged by feel. A corridor 1.2 m wide is enough for daily circulation in a columbarium but in an evacuation it must clear several hundred people in a quarter of an hour. Those are not the same number.

The width factor for level escape is 0.65 m per 100 people; on stepped sections, 0.75 m. These are the values commonly used in the fire code for building design.
With 300 people in the building, total clear escape width is 300 ÷ 100 × 0.65 = 1.95 m, rounded to 2.0 m.
That 2.0 m is the sum of the clear widths of all exits, not a single corridor. Two 1.0 m doors give 2.0 m in total, which is just sufficient.
No individual escape route may be narrower than 1.4 m clear. This is a second constraint, applied at the same time as the total.
If a secondary route in a columbarium is only 0.9 m, the flow rate on that route becomes the bottleneck even when the total is adequate. People jam at the narrow point and the width further on counts for nothing.
Escape width is measured clear, not as the structural opening.
A 1.2 m opening with a 50 mm door leaf gives roughly 1.1 m clear when open. If the leaf swings against the escape direction the leaf thickness is deducted again; add a door closer and deduct another 50 mm.
Finishes eat width too: a 30 mm architrave, 20 mm stone facing on each side, and a 1.2 m door can be down to 1.05 m in reality Calculate escape width in a columbarium on finished clear dimensions.
Escape doors open in the direction of escape, with no threshold and no revolving door.
No steps within 1.4 m inside the door. Two steps in a columbarium foyer become a trip hazard during evacuation.
Doors must be openable from inside by hand, without a key or a card. If a back-of-house door in a columbarium is locked, it must have a push bar.
Every fire compartment needs at least two means of escape, and adjacent exits must be at least 5 m apart horizontally.
Closer than 5 m and two exits behave as one, because the crowd funnels to the same side.
A small columbarium with a single exit must be verified against the code — area, occupant number and travel distance all satisfied — and that exit must lead directly outside.

Niche row spacing of 1.5 m becomes the escape path in an evacuation.
So row spacing may not be less than 1.2 m (single person), and a cross aisle 1.5 m wide must connect to the main route every 15–20 m.
With 1.0 m row spacing and no cross aisles, evacuees walk a single long slot to the end, and travel distance far exceeds the limit.
Escape width is calculated on people present at one time, not on total niche count.
The estimate: peak-hour flow × average dwell time ÷ 60. A peak hour of 400 with a 45-minute stay gives 300 people present.
People standing in the ceremony area are counted at 1.2 m² each, people in motion at 0.5 m². If the area in front of the Buddha image is packed, the real density exceeds this and width should be taken at the upper bound.
Estimating from floor area. Niche zones are large but sparsely occupied, so area-based counting overestimates; ceremony areas are small but crowded, so it underestimates.
Ignoring the width lost to finishes. Drawn at 1.2, built at 1.05.
Exits grouped on one side. Two doors in the same wall 3 m apart are one door.
Q: Do niche-zone aisles count toward escape width?
A: Yes. Niche aisles are part of the escape path, and they are the first section to block.
Q: Can escape doors be automatic?
A: Not on their own. An automatic door must be manually openable when the power fails, with clear signage showing how to push it open.
Q: How wide should stairs be?
A: At 0.75 m per 100 people, and not less than 1.2 m. If a columbarium stair doubles as an escape route, treads and landings must meet escape requirements.

Escape width in a columbarium: 0.65 m per 100 people (0.75 on stairs), 1.4 m total minimum measured clear after finishes doors swinging in the escape direction with no threshold, at least two exits 5 m apart, row spacing used as escape path with cross aisles, and occupancy estimated as peak flow times dwell time. A columbarium speaks of stillness in normal times and speed in an evacuation — where the two meet in the same set of dimensions, satisfy speed first, then talk about stillness.