Emergency lighting is invisible in normal times and only proves itself when something fails. A columbarium's characteristics are long corridors, dense niche zones, many elderly users and few exits. One power cut without compliant emergency lighting leaves hundreds of people standing in the dark, afraid to move.

The minimum illuminance on the floor of an escape route is 1 lux. That is the code floor. For a columbarium, aim for 3 lux, because many users are elderly and 1 lux only shows outlines.
To put 1 lux in perspective: a road under moonlight is about 0.5–1 lux. An escape route in a columbarium needs to be three times brighter than moonlight for people to walk steadily.
Emergency lighting must sustain at least 90 minutes. Where a columbarium has large niche areas and long escape distances, aim for 120.
The point of 90 minutes is that everyone gets out. In a facility with 3,000 niches and 400 people at Qingming peak, full evacuation takes about 15 minutes, so 90 leaves ample margin.
Place emergency luminaires along the escape route at 3–5 m centres, mounted at 2.5 m (wall) or on the ceiling.
They are mandatory at corners, stair heads and directly above doors. These are decision points, where a person has to know which way to go.
Do not blanket the interior of niche zones. Fit them only at each zone exit and where the zone meets the main route. Filling the niche zones produces the opposite of safety: in a blackout, patches of brightness make the route itself look darker.
Provide exit signs in both illuminated and photoluminescent versions.
The illuminated type is on the emergency circuit and runs 90 minutes on battery. The photoluminescent type needs no power; it charges by day and still glows for 4–6 hours in a total outage.
An illuminated-only installation goes fully dark once the battery fails. A photoluminescent-only installation is too dim when it has not charged enough during the day.
Emergency lighting requires two sources: a dual-circuit mains supply with automatic end-of-line transfer.
Where possible, add a generator or a central EPS unit. The fire load category of a columbarium follows building size, and beyond a certain scale a dual supply is mandatory.
Keep the emergency circuit separate from general lighting, and label the board "fire services supply — do not isolate".

Test emergency lighting on schedule.
Monthly. Press the test button for 30 seconds and confirm every luminaire lights.
Quarterly. Run a 30-minute discharge test and check battery capacity.
Annually. Full-load discharge for 90 minutes, recording the duration of each luminaire Anything below 60 minutes is replaced as a batch.
Keep the records on file in the fire control room. The first thing a fire inspection asks for is that book; if it is blank, a columbarium's safety is an empty phrase.
Niche zones go dark in an outage, and this is where problems concentrate.
Method: fit a low-level floor luminaire at the end of every row (300 mm above floor), battery-backed, 3–5 W. With that small amount of light in a niche zone, people do not panic.
Run the cable in a conduit under the floor rather than on the wall. In a columbarium the walls are the niches; wall-mounted fittings conflict with the carcasses.
Exits lit, route dark. The exit signs glow, the path is black, and nobody reaches the exit.
Fittings too high. Mounted above 4 m, floor illuminance is insufficient and maintenance needs scaffolding.
Batteries past their life. Battery life is 3–5 years; unchanged batteries are decoration. "The lamp lights but only lasts five minutes" is the most common hidden failure in a columbarium.
Emergency luminaires hidden by decoration. Ceiling features, light coves and stretch membranes routinely swallow them.
Q: Can emergency and general lighting share the same fittings?
A: Yes — battery-backed emergency versions — provided they switch automatically to emergency mode on power failure.
Q: Is a centrally monitored system needed?
A: Advisable for larger facilities. Central monitoring runs automatic self-tests and removes the need to test each luminaire by hand.
Q: Do floor-level luminaires spoil the everyday look?
A: Low, small and warm, they are almost invisible in normal use. In a columbarium they damage the atmosphere far less than a row of emergency luminaires on the ceiling.

Emergency lighting in a columbarium: 3 lux on the route (against a code minimum of 1), 90 minutes duration, 3–5 m spacing, 2.5 m mounting height, mandatory at corners and doors, illuminated plus photoluminescent signage, dual supply with end-of-line transfer, 30-second monthly and 90-minute annual tests, and 300 mm floor luminaires at row ends. The safety of a columbarium is measured by whether every one of those lamps is still lit in that ninetieth minute.